+86-17362949750

+86-27-65526007

NEWSnews

Present Position:Home > News > Technical Article

Relay Protection Test Set: Differential, Auto-Reclosing & DI/DO Wiring

Time:2026-11-11 Number:14

Chapter 7 In-Depth Analysis of Differential Protection Tests

6.1 Comparison of the Single-Phase and Three-Phase Methods


6.2 Verification Steps for the Restraint Characteristic Curve

1. Determine the working points: Select several (Ir, Id) combinations covering the pickup section, the percentage restraint section, and the high restraint section;

2. Calculate the injection quantities: Derive the two-side injection currents I1’ and I2’ from Ir and Id;

3. Point-by-point measurement: At each working point, judge whether the protection operates after the test set injects;

4. Plot the characteristic curve: Overlay the measured operating boundary points with the set characteristic curve and check whether the requirements are met;

5. Harmonic restraint verification: At a working point where the differential current already exceeds the pickup value, superimpose the second harmonic to verify that harmonic restraint is correctly applied.

Chapter 8 Auto-Reclosing and Post-Acceleration Tests

7.1 Verification of the Auto-Reclosing Time

Auto-reclosing operating time error: Δt_AR = t_AR.act - t_AR.set

Reference acceptance criterion (subject to the device technical specification): |Δt_AR| ≤ 50 ms

7.2 Complete Test Sequence

Step 1  Normal state (HWJ=1, TWJ=0), output normal three-phase current and voltage

Step 2  Switch to fault quantities (current above the setting) → start timing
       Test set DI acquires the protection trip signal → record operating time t1

Step 3  Switch the circuit breaker position: HWJ→0, TWJ→1
       Clear the current, start auto-reclosing timing

Step 4  Wait for the auto-reclosing set time t_AR.set

Step 5  Protection issues a close command → test set acquires it, record t_AR.act

Step 6A (transient fault verification) Restore normal current → reclosing succeeds, protection does not operate again ✓
Step 6B (permanent fault verification) Apply the fault current again → post-acceleration operates → record post-acceleration time t_acc ✓

7.3 Post-Acceleration Operating Time

The post-acceleration set time delay is usually 0–0.3 s (subject to the device settings). The test set must complete the full “first trip → breaker open position → reclose” sequence before the post-acceleration logic can be triggered; if the reclosing step is skipped and the fault is applied again directly, the post-acceleration protection will not operate.

Chapter 9 Wiring Logic and Digital Input / Output Details


Diagram: Wiring / Injection Logic Diagram

8.1 Current Only vs. Both Current and Voltage Required

8.2 Principles for Allocating Digital Inputs and Outputs

8.3 Standard Operating Procedure

1. Wiring and power-on check: Confirm CT secondary short-circuiting, correct phase sequence, and DI/DO contacts in place;

2. Select the test template: Load the automated template for the corresponding protection type;

3. Enter the setting parameters: Pay attention to primary value → secondary value conversion (see Section 6.1);

4. Pre-operation check: Confirm that the magnitude and phase of the output quantities match expectations;

5. Apply test quantities and acquire results: Record the operating time, operating current, etc.;

6. Result judgment: Judge qualification according to the device technical specification and relevant standards;

7. Restore wiring and complete the records: Restore the secondary circuit and archive the test report.