ZXBLQ-II Zinc Oxide Arrester Tester
ZXBLQ-II zinc oxide arrester tester is a special instrument used to test the electrical performance of zinc oxide arrester. The instrument is suitable for live or power failure detection of zinc oxide arrester of various voltage levels, so as to timely detect the internal insulation damp and valve aging and other dangerous defects.
ZXBLQ-II zinc oxide arrester tester is easy to operate and easy to use. The whole measuring process is controlled by single chip microcomputer. It can measure the total current, resistive current and its harmonics, power frequency reference voltage and its harmonics, active power and phase difference. The instrument uses digital waveform analysis technology, harmonic analysis and digital filtering software anti-interference methods to make the measurement results accurate and stable.
1. This machine adopts large screen LCD display, all English menu operation, easy to use.
2. High precision sampling and processing circuit and advanced Fourier harmonic analysis technology ensure more reliable data.
3. The instrument adopts high-speed magnetic isolation digital sensor to directly collect the input voltage and current signals, which ensures the reliability and safety of the data.
4. Support wireless synchronous voltage sampling mode (type II).
5. The instrument can use electric field induction instead of PT secondary wiring (type I).
6. It has the functions of resistive current fundamental peak output and side phase correction.
7. The instrument is equipped with rechargeable battery, calendar clock and micro printer, which can store 120 sets of measurement data.
1. Full current measurement range: 0-10mA effective value, 50Hz/60Hz accuracy: ± (reading × 5% + 5μa)
2. Measurement accuracy of resistive current fundamental wave (secondary method without Interphase Interference): ± (reading × 5% + 5μa)
3. Current harmonic accuracy: ± (reading × 10% + 10μa)
4. Reference voltage input range: 25V-250V RMS, total harmonic content < 30% 50Hz/60Hz
5. Reference voltage measurement accuracy: ± (reading × 5% + 0.5V)
6. Voltage harmonic measurement accuracy: ± (reading × 10%)
7. Angle between fundamental current and fundamental voltage: 0-360°
8. Working time of battery: 6 hours of main engine charging power supply: 220 V ± 10% 50Hz/60Hz charging time: 5 hours
9. Host volume: 325 × 280 × 140
10. Host weight: 3.5kg (without cable)
11. Working environment: temperature: - 10-50 ℃, humidity: < 90%
-