+86-17396104357

+86-27-65526007

Home > Products > ZX3030C Portable Three Phase Testing Device

ZX3030C Portable Three Phase Testing Device

ZX3030C Portable Three Phase Testing Device adopts luxurious aluminum alloy case and detachable aluminum alloy hanging table frame. It is suitable for the inspection of various three-phase electric energy meters of class 1.0 and below.

Features
Technical indicators

1. Instrument accuracy level: 0.05 or 0.1

2. PC connection terminal: RS232 communication interface

3. Three phase source parameters

1)output voltage:

       3*57.7V Y 3*100V

        3*220V Y 3*380V 

Regulation range: 0~120% continuously adjustable, fineness:better than 0.01%

2)Output current

Range: 25mA、0.1A、1A、5A、25A、100A

Minimum output current: 1mA ( accuracy <5%)

3)Output power: voltage circuit 3×50VA  

voltage circuit 3×150VA  

4).Stability of output voltage current power : ≤0.02%/120S

5).Output voltage current waveform distortion: ≤ 0.5%

6).Three phase degree of symmetry: better than 120o±0.3o  

7).Frequency range: 45Hz~65Hz regulation fineness: 0.1Hz

8).Phase range: -180.0° ~180.0°regulation fineness: 0.1°

9). Indicating instrument accuracy level:

voltmeter,ammeter ±0.01%

Phase meter accuracy ±0.01°

Frequency meter accuracy: ±0.01Hz

4. Built-in three phase standard meter parameters:

1) Input voltage

scope: 40-480V

Input voltage range: 60、120、240、480

overload capacity: 600V

input load ≤0.5mA(480V)

2) Input current

Scope: 0.01 - 100A

Range: 100、50、25、10、5、2.5、1、0.5、0.25、0.1、0.05、0.025A

Overload capacity: 150A

3) Accuracy:

Level: 0.05 (0.1A~120A)

Power measuring accuracy:

Active power measuring accuracy: 0.05%/0.1%(PF≥0.5)

Reactive power measuring accuracy: 0.1%/0.2%(PF≥0.5)

4) electric energy measuring accuracy

Active power measuring accuracy: 0.05%/0.1%(PF≥0.5)

Reactive power measuring accuracy: 0.1%/0.2%(PF≥0.5)

5. protection function:

voltage short circuit, current open circuit, over-load, display over-voltage protection

6. can do 2~21th order harmonic test, voltage interruption and drop test, harmonic amplitude adjustable

7. power supply: 230V±10%~50Hz

8. Maximum power consumption: 300VA

9. Working environment: temperature 20℃±5℃ relative humidity≤85%

Service commitment